Productos convencionales

FPC-7034 Extensión IDC, 4 puntos


  • Adds four Class B (Style B) or Class A (Style D) initiating circuits to the FPD‑7024 FACP
  • For use with normally‑open (NO) or normally‑closed (NC) alarm contacts
  • Compatible with two‑wire or four‑wire smoke detectors
  • Up to 20 two‑wire smoke detectors per circuit
  • Easy installation due to plug‑in design and screw terminal circuit connections
  • No programming necessary

Descripción

Environment: Indoor, dry
Relative Humidity: Up to 95%, non‑condensing
Temperature (operating): +32°F to +122°F (0°C to +50°C)
Dimensions (HxWxD): 2.0 in. x 4.5 in. x 1.3 in. (5.1 cm x 11.4 cm x 3.3 cm)
Response Time: Choice of fast (500 ms) or programmable from 1 sec to 89 sec
per initiating circuit:
Alarm Current (short circuit): 40 mA maximum
Alarm Current (threshold): >25 mA
Detector Standby Current (total): 3 mA maximum
Loop Supervision Current: 8.0 mA to 15.0 mA
Trouble Current Threshold: <7 mA
Voltage (supply): 18.0 VDC to 25.5 VDC
per FPC‑7034 module:
Current (standby): 60 mA maximum
Current (alarm): 160 mA maximum

Documentos

TituloTipoIdioma
Hoja de DatosPDFen-US