| FCP‑500(‑P): |
Scattered light measurement |
| FCP‑500‑C(‑P): |
Combination of scattered light measurement and CO algorithm |
| All FCP‑500 detectors: |
Drift compensation for smoke sensor baseline (optical sensors) |
| Air Speed |
300 ft/min (1.5 m/s) maximum |
| Humidity |
95% (non-condensing) |
| Interference Immunity: |
According to UL 268 |
| Operating Temperature |
+32 °F to +100 °F (0°C to +38°C) |
| Protection Category: |
FAP‑500(‑C): IP 53 FAP‑500(‑C)‑P: IP 33 |
| Color: |
|
| Detector Housing: |
White |
| Detector Front Plate: |
FCP-500(-C): white FCP-500(-C)-P: transparent (color inserts) |
| Dimensions (diameter x D) |
|
| Detector: |
4.5 in. x 2.2 in. (11.4 cm x 5.6 cm) |
| Detector with Trim Ring: |
5.9 in. x 2.2 in. (15 cm x 5.6 cm) |
| Detector with Trim Ring and Base: |
5.9 in. x 2.75 in. (15 cm x 7 cm) |
| Material: |
Polycarbonate |
| Area Monitored: |
Refer to NFPA 72 Guideline |
| Mounting Height: |
Maximum: Refer to NFPA 72 Guidelines Minimum: 9 ft (2.7 m) |
| False Ceiling |
|
| Clearance (minimum): |
6 in. (15.2 cm) with tolerances of -0.0625 in. (1.6 mm) and +0.1875 in. (4.8 mm) |
| Mounting Hole: |
5.0625 in. (12.9 cm) |
| Thickness (maximum): |
1.25 in. (3.2 cm) |
| Alarm |
|
| Output: |
Alarm output through normally-open (NO) relay in FCA‑500 base. An alarm resistance of 0 Ω or 680 Ω in series to the relay can be chosen. |
| Relay Rating: |
1 A at 30 VDC |
| Reset Time |
The detector resets if power is interrupted for at least 2 sec. |
| Display |
|
| Two-color LED: |
Red = alarm, green = test mode, normal |
| Remote LED: |
Normally-open (NO) relay connects ground through 1.5 kΩ, 20 mA maximum |
| Trouble |
|
| Output: |
Trouble output through normally-closed (NC) relay in FCA-500 base |
| Relay Rating: |
1 A at 30 VDC |
| Current Consumption |
|
| FCA‑500 Base |
Alarm: 47 mA Standby: 3.5 mA |
| FCA‑500‑E Base |
Alarm: 47 mA Standby: 24 mA |
| Operating Voltage |
|
| Four‑wire: |
9.7 VDC to 30 VDC |