| Reverberant* sounder output (dBA) |
|
| Temporal pattern (position 1) |
12 or 24 V nominal* , 76 dBA |
| Continuous pattern (position2) |
12 or 24 V nominal* , 80 dBA |
| * Minimum dB rating for operational voltage range per UL 464 |
|
| Sounder current draw (mA) |
|
| Temporal pattern (position 1) |
12 V nominal*24 V nominal* , DC = 191, FWR = 262DC = 138, FWR = 166 |
| Continuous pattern (position 2) |
12 V nominal*24 V nominal* , DC = 292, FWR = 384DC = 138, FWR = 208 |
| * Minimum dB rating for operational voltage range per UL 464. |
|
| Voltage: |
|
| Nominal (regulated) |
12 VDC/FWR or 24 VDC/FWR |
| Range |
8 to 17.5 VDC/FWR or 16 to 33 VDC/FWR |
| Range with synch module |
8.5 to 15.5 VDC/FWR or 16.5 to 33 VDC/FWR |
| Humidity |
10% to 93%, noncondensing |
| Temperature (operating) |
+32°F to +120°F (0°C to +49°C) |
| Sounder dimensions LxWxH) |
5.6 in. x 4.7 in. x 1.3 in. (142 mm x 119 mm x 33 mm) |
| Frequency range |
520 Hz ± 10% |
| Wave form |
Square wave |