GEC24-15/75WR Altavoz/luz estrob. techo, 15/75cd 24V


  • Silence the horn while strobes flash
  • Evacuation tone
  • Use the SuperSlide feature for easy testing
  • Wide voltage range; 16 to 33 VDC or FWR
  • Select high or low frequency, high or low volume, and temporal Code 3 or continuous tone pattern
  • Rugged die‑cast metal mounting plate

Descripción

Input voltage 24 VDC or VFWR nominal
Voltage range 16 to 33 VDC or FWR
Strobe Current (maximum) 96 mA RMS; 135 mA FWR
Relative Humidity Up to 93% non‑condensing
Temperature (Operating) +32°F to +120°F (0°C to +49°C)
Horn (Continuous, 2400 Hz)
Audible Device Current (maximum) 28 mA RMS; 48 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 86 dBA; Low output: 78 dBA
Horn (Continuous, Mechanical)
Audible Device Current (maximum) 25 mA RMS; 44 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 84 dBA; Low output: 76 dBA
Horn (Temporal Code 3, 2400 Hz)
Audible Device Current (maximum) 28 mA RMS; 48 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 83 dBA; Low output: 75 dBA
Horn (Temporal Code 3, Mechanical)
Audible Device Current (maximum) 25 mA RMS; 44 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 81 dBA; Low output: 73 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
Chime (Continuous)
Audible Device Current (maximum) 15 mA RMS; 30 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 71 dBA*; Low output: 68 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
Chime (Temporal Code 3)
Audible Device Current (maximum) 15 mA RMS; 30 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 71 dBA*; Low output: 68 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.
Whoop
Audible Device Current (maximum) 56 mA RMS; 62 mA FWR
Sound output (maximum range) at 10 ft (3 m) High output: 83 dBA; Low output: 72 dBA*
* If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application.