| Input voltage |
12 VDC or FWR nominal |
| Voltage range |
8 to 17.5 VDC or FWR |
| Strobe current ratings: |
|
| 15 cd |
163 mA RMS |
| 30 cd |
212 mA RMS |
| 60 cd |
331 mA RMS |
| 75 cd |
436 mA RMS |
| Relative Humidity |
Up to 93% non‑condensing |
| Temperature (Operating) |
+32°F to +120°F (0°C to +49°C) |
| Dimensions (H x W x D) |
5.0 in. x 4.5 in. x 2.5 in. (12.7 cm x 11.4 cm x 6.4 cm) |
| Horn (Continuous, 2400 Hz) |
|
| Audible Device Current (maximum) |
29 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
79 dBA to 84 dBA |
| Horn (Continuous, Mechanical) |
|
| Audible Device Current (maximum) |
26 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
79 dBA to 83 dBA |
| Horn (Temporal Code 3, 2400 Hz) |
|
| Audible Device Current (maximum) |
29 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
76 dBA to 81 dBA |
| Horn (Temporal Code 3, Mechanical) |
|
| Audible Device Current (maximum) |
26 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
75 dBA to 80 dBA |
| Chime (Continuous) |
|
| Audible Device Current (maximum) |
13 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
64 dBA* to 65 dBA* |
| * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application. |
|
| Chime (Temporal Code 3) |
|
| Audible Device Current (maximum) |
13 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
63 dBA* to 64 dBA* |
| * If you operate the horn in this mode at this voltage, it does not meet the UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Use the high output setting for public mode application. |
|
| Whoop |
|
| Audible Device Current (maximum) |
55 mA RMS |
| Sound Output (maximum range) at 10 ft (3 m) |
77 dBA to 83 dBA |