| Current (operating strobe): |
15 cd = 72 mA; 30 cd = 88 mA; 75 cd = 176 mA; 95 cd = 200 mA; 115 cd = 214 mA, 150 cd = 286 mA |
| Regulated Voltage (input): |
24 VDC or FWR |
| Temperature (Operating): |
+32°F to +120°F (0°C to +49°C) |
| Candela Selections: |
15 cd, 30 cd, 75 cd, 95 cd, 115 cd, or 150 cd |
| Dimensions (diameter x D): |
6.0 in. x 2.6 in. (15.2 cm x 6.6 cm) |
| Temporal Code 3, 2400 MHz Mode |
|
| Audible Device Current (maximum): |
22 mA RMS45 mA FWR |
| Sound Output (maximum range)at 10 ft (3 m): |
High output: 83 dBALow output: 75 dBA |
| Temporal Code 3 Mechanical Mode |
|
| Audible Device Current (maximum): |
23 mA RMS43 mA FWR |
| Sound Output (maximum range)at 10 ft (3 m): |
High output: 81 dBALow output: 73 dBA* |
| *Operating the horn in this mode at this voltage does not meet the minimum UL reverberant sound level required for public mode fire protection service. These settings are acceptable only for private mode fire alarm use. Chime mode is only acceptable for private use. |
|
| Continuous 2400 MHz Mode |
|
| Audible Device Current (maximum): |
22mA RMS45 mA FWR |
| Sound Output (maximum range) at 10 ft (3 m): |
High output: 86 dBALow output: 78 dBA |
| Continuous Mechanical Mode |
|
| Audible Device Current (maximum): |
23 mA RMS43 mA FWR |
| Sound Output (maximum range)at 10 ft (3 m): |
High output: 84 dBALow output: 76 dBA |