| Rated load impedance (output power) |
|
| 100 V |
20 Ω (500 W) |
| 70 V |
10 Ω (500 W) |
| Rated output power, 1 kHz, THD ≤ 1% |
2 ✕ 500 W1 |
| Rated input voltage |
+6 dBu |
| Max. RMS voltage swing, 1 kHz, THD ≤ 1%, without load |
|
| 100 V |
110 V |
| 70 V |
78 V |
| Voltage gain, ref. 1 kHz, fixed |
|
| 70 V |
33.2 dB |
| 100 V |
36.2 dB |
| Maximum load capacitance |
2 µF |
| Input level, max. |
+18 dBu (9.75 Vrms) |
| Frequency response, ref. 1 kHz, rated load, -3 dB |
50 Hz to 25 kHz |
| Input impedance, active balanced |
20 kΩ |
| Signal-to-noise ratio (A-weighted) |
> 104 dB |
| Output noise (A-weighted) |
< -62 dBu |
| Crosstalk , ref. 1 kHz |
< -85 dB |
| Output stage topology |
Class-D, transformer, floating |
| Power requirements |
|
| Power supply |
Mains: 115-240 VAC ±10%, 50/60 Hz (2) Battery: 21-32 VDC |
| Power consumption |
Pmax – 3dB * / idle **/ Standby 230VAC, 50Hz: 700W / 21W / 1.9W120VAC, 60Hz: 745W / 18W / 1.5W24VDC, 60Hz: 735W / 16W / 1.5W * Alarm, ** No audio (pilot tone) |
| Inrush current |
2 A |
| Inrush current, after five-second power cycle |
1.3 A |
| Mains fuse |
T6.3A (internally) |
| DC fuse |
30A (internally) |
| Ground fault |
R < 50 kΩ |
| CAN BUS port |
2 ✕ RJ-45, 10 to 500 kbit/s |
| Protection |
Audio input level limiter, RMS output power limiter, high temperature, DC, short circuit, mains undervoltage protection, DC supply undervoltage protection, inrush current limiter, ground fault |
| Cooling |
Front-to-rear, temperature-controlled fans |
| Operating temperature |
-5 °C to +45 °C (+23 °F to +113 °F) |
| Storage temperature |
-40 °C to +70 °C (-40 °F to +158 °F) |
| Humidity (non-condensing) |
5% to 90% |
| Altitude |
Up to 2000 m |
| Dimensions (HxWxD) |
88 mm x 483 mm x 375 mm (2RU) |
| Weight (net) |
16.5 kg |
| Mounting |
Standalone; 19 in. rack |
| Color |
Black with silver |