Fuentes de alimentación y productos de supervisión

AL400UL-PD4R Fuente aliment./cargador incendio, 4A


  • Four fuse-protected, Class 2 Rated, power‑limited outputs
  • 12 VDC or 24 VDC selectable output
  • Outputs are filtered and electronically regulated
  • Main power input fuse rated at 3.5 A, 250 V
  • Short circuit and thermal overload protection
  • Built‑in charger for sealed lead‑acid or gel‑type batteries

Descripción

Current Draw (input): 1.45 A
Voltage (supply): 115 VAC, 60 Hz
Color: Red
Dimensions (H x W x D): 13 in. X 13.5 in. x x 3.25 in. (33 cm x 34.3 cm x 8.3 cm)
Battery Charging: Maximum charge rate is 0.7 A
Number: Four fused 12 VDC or 24 VDC selectable, power‑limited
Ratings
Fuses: 3.5 A, 250 V
Power: 4 A at 12 VDC or 3 A at 24 VDC
AC Fail: Form C contacts rated for 1 A at 30 VDC. Relay normally energized when AC power is present. Fail condition report sent approximately 1 min after AC power loss.
Battery Presence: Form C contacts rated for 1 A at 30 VDC. Relay normally energized when DC power is present. Fail condition report sent approximately 3 min after battery remains undetected.
Low Battery: Form C contacts rated for 1 A at 30 VDC. Relay normally energized. Report sent when DC power drops to 10.5 VDC for 12 VDC setting or 21 VDC for 24 VDC setting.

Documentos

TituloTipoIdioma
Hoja de DatosPDFen-US