| Relative Humidity: |
Up to 95%, non‑condensing |
| Temperature (Operating): |
+32°F to +120°F (0°C to +49°C) |
|
|
| Candela Selections: |
15 cd, 15/75 cd*, 30 cd, 75 cd, 95 cd, 115 cd, or 177 cd |
| Dimensions(diameter x D): |
6.8 in. x 2.4 in. (17.3 cm x 6.1 cm) |
| Horn Audibility (UL Reverberant Room)at 10 ft (3 m): |
75 dBA |
| Material: |
Molded plastic enclosure incorporating a Xenon flashtube. |
| Weight: |
5.3 oz. (150 g) |
|
|
| Maximum Operating Horn Current: |
24 VDC: 57 mA RMS 24 FWR: 57.5 mA RMS |
| Maximum Operating Current (24 VDC): |
15 cd: 121 mA RMS 15/75 cd: 135 mA RMS 30 cd: 170 mA RMS 75 cd: 262 mA RMS 95 cd: 331 mA RMS 115 cd: 382 mA RMS 177 cd: 546 mA RMS |
| Maximum Operating Current (24 VFWR): |
15 cd: 125.5 mA RMS 15/75 cd: 134.5 mA RMS 30 cd: 164.5 mA RMS 75 cd: 254.5 mA RMS 95 cd: 296.5 mA RMS 115 cd: 355.5 mA RMS 177 cd: 456.5 mA RMS |
| Voltage (Nominal Input): |
24 VDC or FWR unfiltered |
| Voltage (Operating Range): |
16 V to 33 V with Sync•Circuit™ module: 27 V to 33 V |
|
|
| Sync•Circuit™ is a trademark of System Sensor® in the United States and other countries. |
|
| System Sensor® is a registered trademark or a trademark of Pittway International, Ltd. in the United States and other countries. |
|