PA- Commercial Sound and Emergency Sound

LBB1990/00 Controlador


  • Núcleo del Sistema de alarma por voz Plena
  • Con certificación EN 54‑16 y compatible con EN 60849
  • Gestor de mensajes y amplificador de 240 W incorporado
  • Salidas de seis zonas
  • 6 de emergencia y 6 de activación

Descripción

Mains power supply
Voltage 230/115VAC, ±15%, 50/60 Hz
Current inrush 8 A
Max power consumption 600 VA
Battery power supply
Voltage 24 VDC, +15% / -15%
Current max 14 A
Performance
Output power (rms/maximum) 240 W / 360 W
Power reduction on backup power -1 dB
Frequency response 60 Hz to 18 kHz (+1/-3 dB at -10 dB ref. rated output)
Distortion <1% at rated output power, 1 kHz
Bass control -8/+8 dB at 100 Hz
Treble control -8/+8 dB at 10 kHz
Mic/line input 1 x
Connector XLR, 6.3 mm jack
Sensitivity 1 mV (mic), 1 V (line)
Impedance >1 kohm (mic); >5 kohm (line)
S/N (flat at max volume) >63 dB (mic); >70 dB (line)
S/N (flat at min volme/muted) >75 dB
CMRR >40 dB (50 Hz – 20 kHz)
Headroom >25 dB
Speech filter -3 dB at 315 Hz, high-pass, 6 dB/oct
Phantom power supply 12 V (mic mode only)
VOX trigger level -20 dB (100 µV mic / 100 mV line) or via input contact
Limiter Automatic
Line input (BGM and PC call station)
Connector Cinch, stereo converted to mono, unbalanced
Sensitivity 200 mV
Impedance 22 kohm
S/N (flat at max volume) >70 dB
S/N (flat at min volume/muted) >75 dB
Headroom >25 dB
Trigger Inputs 12 x (6 EMG, 6 business)
Connectors MC1,5 / 14-ST-3,5
Activation Programmable
Supervision On EMG inputs, programmable
Supervision method Series / parallel resistor
100 V input
Connector MSTB 2,5 /16-ST
Power handling capacity 1000 W
Tape output 1 x
Connector Cinch, 2 x mono
Nominal level 350 mV
Impedance <1 kohm
Loudspeaker outputs
Connectors MSTB 2,5 /16-ST, floating
100 V output 700 W rated per zone
Volume override types 3-wire, 4-wire (24 V), 4-wire failsafe
BGM zone output Attenuation 70 / 50 /35 /25 / 18 / 13 V for0 / -3 / -6 / -9 / -12 / -15 dB120 / 60 / 30 / 15 / 8 /4 W
Output Contacts
Connector Type MC 1,5/14-ST-3,5
Rating 100 V, 2A, voltage free
Emergency active relay NO / COM / NC
Call active relay NO / COM / NC
Fault relay NO / COM / NC normally energized (failsafe)
General purpose relays NO / COM
Mains operation
Max power 550 W
-3dB 440 W
-6dB 340 W
Pilot tone* 136 W
Idle 60 W
24 VDC operation
Max power 14.0 A (336 W)
-3 dB 12.5 A (300 W)
-6 dB 9.5 A (228 W)
Pilot tone* 2.5 A (60 W)
Idle 0.9 A (22 W)
Data format WAV-file, 16-bit PCM, mono
Supported sample rates (fs) 24 / 22.05 / 16 / 12 / 11.025 / 8 kHz
Frequency response
at fs=24kHz 100 Hz to 11 kHz (+1/-3 dB)
at fs=22.05kHz 100 Hz to 10 kHz (+1/-3 dB )
at fs=16kHz 100 Hz to 7.3 kHz (+1/-3 dB )
at fs=12kHz 100 Hz to 5.5 kHz (+1/-3 dB)
at fs=11.025kHz 100 Hz to 5 kHz (+1/-3 dB)
at fs=8kHz 100 Hz to 3.6 kHz (+1/-3 dB)
Distortion <0.1% at 1 kHz
S/N (flat at max volume) >80 dB
Memory capacity 16 MB Flash ROM
Recording / playback time 1000 seconds at fs = 8 kHz333 seconds at fs = 24 kHz
Number of messages 255 max
Supervision Flash ROM Continuous checksum control
Supervision DAC 1 Hz pilot tone
Data retention time >10 years
Dimensions (H x W x D) 144 x 430 x 370 mm (19′ wide, 3U high)
Weight Approx. 21.17 kg
Mounting 19”rack
Color Charcoal
Operating temperature -10 ºC to +55 ºC (14 ºF to +131 ºF)
Storage and transport temperature -40 ºC to +70 ºC (-40 ºF to +158 ºF)
Relative humidity <95%
Acoustic noise level of fan <48 dB SPL at 1 m (max output)

Documentos

TituloTipoIdioma
Hoja de DatosPDFes-ES