Productos convencionales

FCP‑500 Conventional Flush‑mount Smoke Detectors


  • Modern, ultra-low profile design
  • Color inserts match the surrounding decor
  • Smooth, easily-cleaned detector surface
  • Innovative retention mechanism
  • High reliability
  • Four-wire technology (six‑conductor wire)
  • Compatible with 12 VDC or 24 VDC systems
  • 30 ft (9 m) spacing between detectors
  • Optional carbon monoxide (CO) sensor for false alarm reduction
  • Dual color LED
  • FCA-500-E Base with integrated end-of-line(EOL) relay

Descripción

FCP‑500(‑P): Scattered light measurement
FCP‑500‑C(‑P): Combination of scattered light measurement and CO algorithm
All FCP‑500 detectors: Drift compensation for smoke sensor baseline (optical sensors)
Air Speed 300 ft/min (1.5 m/s) maximum
Humidity 95% (non-condensing)
Interference Immunity: According to UL 268
Operating Temperature +32 °F to +100 °F (0°C to +38°C)
Protection Category: FAP‑500(‑C): IP 53 FAP‑500(‑C)‑P: IP 33
Color:
Detector Housing: White
Detector Front Plate: FCP-500(-C): white FCP-500(-C)-P: transparent (color inserts)
Dimensions (diameter x D)
Detector: 4.5 in. x 2.2 in. (11.4 cm x 5.6 cm)
Detector with Trim Ring: 5.9 in. x 2.2 in. (15 cm x 5.6 cm)
Detector with Trim Ring and Base: 5.9 in. x 2.75 in. (15 cm x 7 cm)
Material: Polycarbonate
Area Monitored: Refer to NFPA 72 Guideline
Mounting Height: Maximum: Refer to NFPA 72 Guidelines Minimum: 9 ft (2.7 m)
False Ceiling
Clearance (minimum): 6 in. (15.2 cm) with tolerances of -0.0625 in. (1.6 mm) and +0.1875 in. (4.8 mm)
Mounting Hole: 5.0625 in. (12.9 cm)
Thickness (maximum): 1.25 in. (3.2 cm)
Alarm
Output: Alarm output through normally-open (NO) relay in FCA­‑500 base. An alarm resistance of 0 Ω or 680 Ω in series to the relay can be chosen.
Relay Rating: 1 A at 30 VDC
Reset Time The detector resets if power is interrupted for at least 2 sec.
Display
Two-color LED: Red = alarm, green = test mode, normal
Remote LED: Normally-open (NO) relay connects ground through 1.5 kΩ, 20 mA maximum
Trouble
Output: Trouble output through normally-closed (NC) relay in FCA-500 base
Relay Rating: 1 A at 30 VDC
Current Consumption
FCA­‑500 Base Alarm: 47 mA Standby: 3.5 mA
FCA‑500‑E Base Alarm: 47 mA Standby: 24 mA
Operating Voltage
Four‑wire: 9.7 VDC to 30 VDC

Documentos

TituloTipoIdioma
Hoja de DatosPDFen-US