FPD-7024-A Central incendio, 4 z. 24V, Anatel, roja


  • Four initiating zones (expandable to eight); up to 20 two‑wire smoke detectors per zone
  • Programmable through keypads or remote programming software (RPS) through a Conettix interface module
  • Two notification appliance circuits (NACs) on board with a shared internal regulated 24 VFWR, 4 A NAC power supply
  • Easily converts to addressable with the addition of a D7039 Multiplex Expansion Module

Descripción

Current (alarm): 380 mA
Current (standby): 200 mA
Power (primary): 120 VAC, 1.2 A maximum, 60 Hz or 240 VAC, 0.75 A maximum, 50 Hz
* For product‑specific current values, see the product’s Installation Instructions.
Environment: Indoor, dry
Relative Humidity: Up to 95%, non-condensing
Temperature (operating): +32°F (0°C) to +120°F ( +49°C)
Color: Red
Dimensions (HxWxD): 20.8 in. x 15 in. x 4.3 in. (52.8 cm x 38.1 cm x 10.9 cm)
Material: Cold-rolled steel Base: 18 gauge (1.2 mm) Cover: 19 gauge (1.1 mm)
Current: 44 mA maximum per loop
Line resistance: 150 Ω
Voltage: 24 VDC nominal
NAC: 24 VDC nominal, 4 A maximum
On-board Relays: Three Form C contacts rated at 5 A, 28 VDC
Off-board Relays: Up to two D7035 Octal Relay Modules with each providing eight Form C relay outputs; contacts rated 5 A, 28 VDC In an addressable system, up to 20 D7053 Multiplex Input-Output Modules are allowed per bus for a total of 40

Documentos

TituloTipoIdioma
Hoja de DatosPDFen-US