Productos analógicos

FLM-325-IM Monitor contacto para mont. caja post.


  • Digital data communications and power provided over a two-wire circuit
  • Class B circuit for dry contact devices
  • Module address programming (1-254) with the D5070 Analog Device Programmer

Descripción

SLC Applied Voltage (rated range) 25.3 VDC to 39 VDC
SLC Current Consumption Standby: 0.339 mAAlarm: 0.358 mA
Resistance
End of Line Device 10 kΩ, 0.25 W per resistor
Initiating Device Circuit Less than 50 Ω
Environment Indoor dry
Relative Humidity Up to 90%, non‑condensing
Temperature Operating: 0°C to +49°C (+32°F to +120°F) Storage: -30°C to +70°C (-22°F to +158°F)
Dimensions (H x W x D) 2.375 in. x 1.75  in. x 0.5 in. (60.325 mm x 44.45 mm x 12.7 mm)
Weight 20 oz. (0.567 kg)

Documentos

TituloTipoIdioma
Hoja de DatosPDFen-US